Setting Distance Relay Pada Jaringan Transmisi 150 kV Sistem Gorontalo
Abstract
Disturbance on the transmission line can cause disruption of normal flow of a stream, in the transmission line of the most common disorders are short circuit. Distance relay are used as security for the transmission line because of its ability to quickly eliminate interference. In this research, symmetrical components method is used in to analyzing the single-phase short circuit current and two phase – ground in SUTT 150 kV Gorontalo Transmission System. The results were obtained, single-phase short circuit at most 1098,11 Ampere and the smallest is 497,67 Ampere and two phase – ground at most = 1026,91 Ampere and = 650,86 and the smallest is = 442,63 Ampere and = 337,55 Ampere, while the calculation results setting distance relay it is appropriate to avoid the reach selectivity setting exceeding 80% and avoid looping and time settings on zona1 = 0 s zona2 = 0,4 s and zona3 = 0,8 s according to the impedance value of the secondary 1 < 2 as well as on 2 < 3.
Downloads
References
Arismunandar.A.dan Kuwahara,1993.“Buku Pegangan Teknik Tenaga Listrik”. Pradnya Paramita : Jakarta
Arismunandar, A., 1984.” Teknik Teganggan Tinggi”, pradnya paramita : jakarta
Badarudin,2012.“Analisi Perhitungan Setting Relai Jarak Sutet 500 kV Krian-Gresik”, Jurnal Skripsi
Hutauruk. T. S, 1991.“Transmisi Daya Listrik”. Penerbit Erlangga. Jakarta
Kadir Abdul, 1998.“Buku Pegangan Transmisi Tenaga Listrik’’ Universitas Indonesia : Jakarta
Nurhadi, Slamet, 2005. “Studi keandalan sistem kerja rele Proteksi di GI polehan 70/20 kV”, Jurnal Skripsi
Syafar, A. Muhammad, 2010. “Studi Keandalan Distance Relay Jaringan 150 kV GI Tello – GI Pare-Pare”, Jurnal Skripsi
Stevenson,Jr,William D, 1983. “Analisis Sistem Tenaga Listrik”,Erlangga,Jakarta
PT.PLN (Persero). 2011, “Pedoman SUTT-SUTET”,Jakarta
Copyright (c) 2018 Taufiq Ismail Yusuf, Laode Muh. Taslan (Author)
This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.