Setting Distance Relay Pada Jaringan Transmisi 150 kV Sistem Gorontalo

  • Taufiq Ismail Yusuf Universitas Negeri Gorontalo
  • Laode Muh. Taslan Universitas Negeri Gorontalo

Abstract

Disturbance on the transmission line can cause disruption of normal flow of a stream, in the transmission line of the most common disorders are short circuit. Distance relay are used as security for the transmission line because of its ability to quickly eliminate interference. In this research, symmetrical  components method  is used in to analyzing the single-phase short circuit current  and two phase – ground in  SUTT 150 kV Gorontalo  Transmission System. The results were obtained, single-phase short circuit at most 1098,11  Ampere and the smallest is 497,67 Ampere and two phase – ground at most  = 1026,91 Ampere and  = 650,86 and the smallest is  = 442,63 Ampere and  = 337,55 Ampere, while the calculation results setting distance relay it is appropriate to avoid the reach selectivity setting exceeding 80% and avoid looping and time settings on  zona1 = 0 s  zona2 = 0,4 s and zona3 = 0,8 s according to the impedance value of the secondary  1 <  2 as well as on  2 <  3.

Keywords: Transmission, Symmetrical Components, Short circuit, Setting Distace Relay

Downloads

Download data is not yet available.

References

Arismunandar.A.dan Kuwahara,1993.“Buku Pegangan Teknik Tenaga Listrik”. Pradnya Paramita : Jakarta

Arismunandar, A., 1984.” Teknik Teganggan Tinggi”, pradnya paramita : jakarta

Badarudin,2012.“Analisi Perhitungan Setting Relai Jarak Sutet 500 kV Krian-Gresik”, Jurnal Skripsi

Hutauruk. T. S, 1991.“Transmisi Daya Listrik”. Penerbit Erlangga. Jakarta

Kadir Abdul, 1998.“Buku Pegangan Transmisi Tenaga Listrik’’ Universitas Indonesia : Jakarta

Nurhadi, Slamet, 2005. “Studi keandalan sistem kerja rele Proteksi di GI polehan 70/20 kV”, Jurnal Skripsi

Syafar, A. Muhammad, 2010. “Studi Keandalan Distance Relay Jaringan 150 kV GI Tello – GI Pare-Pare”, Jurnal Skripsi

Stevenson,Jr,William D, 1983. “Analisis Sistem Tenaga Listrik”,Erlangga,Jakarta

PT.PLN (Persero). 2011, “Pedoman SUTT-SUTET”,Jakarta

Published
2018-06-13
How to Cite
Yusuf, T. I., & Taslan, L. M. (2018). Setting Distance Relay Pada Jaringan Transmisi 150 kV Sistem Gorontalo. Jurnal Teknik, 16(1), 81-92. https://doi.org/10.37031/jt.v16i1.376
Abstract Views : 79 | DOWNLOAD PDF Views : 463